Transformer Sizing Calculator for California

NEC 2023 transformer sizing math for EV charger installers working in California.

DCFC and large workplace EV deployments in California typically need a dedicated 480 V three-phase service, which means sizing a pad-mount or dry-type transformer against the connected charger load plus the NEC 2023 continuous-load multiplier.

Worked example for California

A 180 kW DC fast charger draws roughly 217 A at 480 V three-phase. Applying the 125% continuous-load factor (180 × 1.25 ≈ 225 kVA), then rounding up to the next standard transformer rating gives a 225 kVA minimum. California's 95°F summer ambient does not directly derate the transformer, but it does push the secondary feeder ampacity down by 0.88× — so the secondary copper has to be sized accordingly.

Code & Utilities

California currently enforces the NEC 2023 edition, adopted in 2023. That includes Article 625 (Electric Vehicle Power Transfer System) requirements: 125% continuous-load sizing on EVSE branch circuits, GFCI protection at outdoor receptacles, and provisions for energy management systems on shared circuits.

Major electric utilities serving California include Pacific Gas & Electric (PG&E), Southern California Edison, San Diego Gas & Electric, LADWP, SMUD. Each has its own service-upgrade timeline, EV rebate availability, and metering rules — confirm them before quoting commercial work.

Climate & Ampacity

Plan EV feeders against a 95°F ambient in California — the resulting NEC 310.15(B) correction of 0.88× is what trims a #6 THWN-2 down to its true continuous rating. Because the correction is below 0.9, conductors that "look fine" on a 30°C ampacity table will not carry their nameplate current here — always derate explicitly.

California takeaway

Coordinate primary-side voltage, impedance, and fault-current specs with Pacific Gas & Electric (PG&E) early — interconnection lead times for new pad-mounts in California can run 6-12 months on commercial DCFC sites.