Grounding Conductor Calculator for Delaware

NEC 2020 grounding conductor math for EV charger installers working in Delaware.

EGC sizing in Delaware follows NEC 2020 Table 250.122, indexed off the upstream OCPD rating, with parallel rules for parallel sets and increased-conductor adjustments under 250.122(B).

Worked example for Delaware

For a 60 A EVSE branch, Table 250.122 calls for a minimum #10 Cu equipment grounding conductor. If you upsize the phase conductors for voltage drop in Delaware's long runs, NEC 250.122(B) requires the EGC to be upsized proportionally.

Code & Utilities

The applicable code in Delaware is the NEC 2020, which the state adopted in 2022. That includes Article 625 (Electric Vehicle Power Transfer System) requirements: 125% continuous-load sizing on EVSE branch circuits, GFCI protection at outdoor receptacles, and provisions for energy management systems on shared circuits.

Delaware's primary EV-relevant utilities are Delmarva Power, Delaware Electric Cooperative, Delaware Municipal Electric. Each has its own service-upgrade timeline, EV rebate availability, and metering rules — confirm them before quoting commercial work.

Climate & Ampacity

Plan EV feeders against a 91°F ambient in Delaware — the resulting NEC 310.15(B) correction of 0.88× is what trims a #6 THWN-2 down to its true continuous rating. Because the correction is below 0.9, conductors that "look fine" on a 30°C ampacity table will not carry their nameplate current here — always derate explicitly.

Delaware takeaway

On DCFC sites with parallel feeder sets, each parallel raceway needs its own full-size EGC — a detail inspectors in Delaware catch frequently on commercial submittals.