Breaker Sizing Calculator for Florida
NEC 2020 breaker sizing math for EV charger installers working in Florida.
Every EVSE branch in Florida is treated as a continuous load per NEC 2020 Article 625 — the OCPD must be sized at 125% of the EVSE's listed maximum draw.
Worked example for Florida
A 40 A continuous EV load requires a breaker rated 50 A (40 × 1.25 = 50.0 A, rounded up to the next standard size). The conductor downstream must carry that 50 A after Florida's 0.88× ampacity correction.
Code & Utilities
Florida currently enforces the NEC 2020 edition, adopted in 2023. That includes Article 625 (Electric Vehicle Power Transfer System) requirements: 125% continuous-load sizing on EVSE branch circuits, GFCI protection at outdoor receptacles, and provisions for energy management systems on shared circuits.
Florida's primary EV-relevant utilities are Florida Power & Light, Duke Energy Florida, Tampa Electric, Florida Public Utilities. Always verify the applicable tariff and any utility-specific requirements (CT cabinets, metering enclosures, demand limiters) at design time.
Climate & Ampacity
In Florida, the 92°F summer ambient drives a 0.88× 75°C ampacity correction. Bake this into every Level 2 and DCFC conductor pick before you commit to a wire size. Because the correction is below 0.9, conductors that "look fine" on a 30°C ampacity table will not carry their nameplate current here — always derate explicitly.
Florida takeaway
Use a 100%-rated breaker only when the panel and breaker are both listed for 100% continuous duty — otherwise the 125% rule applies. Florida inspectors enforce this rigorously on Article 625 work.