Breaker Sizing Calculator for Illinois

NEC 2020 breaker sizing math for EV charger installers working in Illinois.

Every EVSE branch in Illinois is treated as a continuous load per NEC 2020 Article 625 — the OCPD must be sized at 125% of the EVSE's listed maximum draw.

Worked example for Illinois

A 40 A continuous EV load requires a breaker rated 50 A (40 × 1.25 = 50.0 A, rounded up to the next standard size). The conductor downstream must carry that 50 A after Illinois's 0.88× ampacity correction.

Code & Utilities

EV installations in Illinois are governed by the 2020 National Electrical Code, in force since 2022. That includes Article 625 (Electric Vehicle Power Transfer System) requirements: 125% continuous-load sizing on EVSE branch circuits, GFCI protection at outdoor receptacles, and provisions for energy management systems on shared circuits.

In Illinois, you'll most often interconnect with ComEd, Ameren Illinois, MidAmerican Energy. Each has its own service-upgrade timeline, EV rebate availability, and metering rules — confirm them before quoting commercial work.

Climate & Ampacity

Illinois's representative summer design ambient is around 91°F, which yields a 0.88× ampacity correction factor at 75°C terminations per NEC 310.15(B)(1). Because the correction is below 0.9, conductors that "look fine" on a 30°C ampacity table will not carry their nameplate current here — always derate explicitly.

Illinois takeaway

Use a 100%-rated breaker only when the panel and breaker are both listed for 100% continuous duty — otherwise the 125% rule applies. Illinois inspectors enforce this rigorously on Article 625 work.