Grounding Conductor Calculator for New Jersey

NEC 2020 grounding conductor math for EV charger installers working in New Jersey.

EGC sizing in New Jersey follows NEC 2020 Table 250.122, indexed off the upstream OCPD rating, with parallel rules for parallel sets and increased-conductor adjustments under 250.122(B).

Worked example for New Jersey

For a 50 A EVSE branch, Table 250.122 calls for a minimum #10 Cu equipment grounding conductor. If you upsize the phase conductors for voltage drop in New Jersey's long runs, NEC 250.122(B) requires the EGC to be upsized proportionally.

Code & Utilities

New Jersey currently enforces the NEC 2020 edition, adopted in 2021. That includes Article 625 (Electric Vehicle Power Transfer System) requirements: 125% continuous-load sizing on EVSE branch circuits, GFCI protection at outdoor receptacles, and provisions for energy management systems on shared circuits.

In New Jersey, you'll most often interconnect with PSE&G, Atlantic City Electric, JCP&L, Orange & Rockland. Always verify the applicable tariff and any utility-specific requirements (CT cabinets, metering enclosures, demand limiters) at design time.

Climate & Ampacity

New Jersey's representative summer design ambient is around 91°F, which yields a 0.88× ampacity correction factor at 75°C terminations per NEC 310.15(B)(1). Because the correction is below 0.9, conductors that "look fine" on a 30°C ampacity table will not carry their nameplate current here — always derate explicitly.

New Jersey takeaway

On DCFC sites with parallel feeder sets, each parallel raceway needs its own full-size EGC — a detail inspectors in New Jersey catch frequently on commercial submittals.