Wire Size Calculator for South Carolina

NEC 2017 wire size math for EV charger installers working in South Carolina.

Wire sizing in South Carolina is governed by NEC 2017 Table 310.16, with the state's 94°F summer ambient driving a 0.88× correction factor at 75°C terminations per Table 310.15(B)(1).

Worked example for South Carolina

A 50 A continuous EV branch needs a conductor whose corrected ampacity meets or exceeds 50 A. In South Carolina's 0.88× correction, that means picking a conductor whose 30°C-rated ampacity is at least 57 A. For copper THWN-2 in EMT, that typically lands at #6 AWG; aluminum requires one to two sizes larger.

Code & Utilities

The applicable code in South Carolina is the NEC 2017, which the state adopted in 2018. That includes Article 625 EVSE rules and the 125% continuous-load factor on charging branch circuits, though some 2020-cycle changes (like expanded EMS provisions) are not yet enforced statewide.

Major electric utilities serving South Carolina include Duke Energy Carolinas SC, Dominion Energy South Carolina, Santee Cooper. Their make-ready, time-of-use, and demand-charge structures vary widely; pull the specific tariff before sizing service equipment.

Climate & Ampacity

South Carolina's representative summer design ambient is around 94°F, which yields a 0.88× ampacity correction factor at 75°C terminations per NEC 310.15(B)(1). Because the correction is below 0.9, conductors that "look fine" on a 30°C ampacity table will not carry their nameplate current here — always derate explicitly.

South Carolina takeaway

Don't forget conduit-fill derating per NEC 310.15(C)(1) when more than three current-carrying conductors share a raceway — a common condition on multifamily and workplace EVSE home-run racks in South Carolina.