Grounding Conductor Calculator for Washington

NEC 2020 grounding conductor math for EV charger installers working in Washington.

EGC sizing in Washington follows NEC 2020 Table 250.122, indexed off the upstream OCPD rating, with parallel rules for parallel sets and increased-conductor adjustments under 250.122(B).

Worked example for Washington

For a 60 A EVSE branch, Table 250.122 calls for a minimum #10 Cu equipment grounding conductor. If you upsize the phase conductors for voltage drop in Washington's long runs, NEC 250.122(B) requires the EGC to be upsized proportionally.

Code & Utilities

The applicable code in Washington is the NEC 2020, which the state adopted in 2023. That includes Article 625 (Electric Vehicle Power Transfer System) requirements: 125% continuous-load sizing on EVSE branch circuits, GFCI protection at outdoor receptacles, and provisions for energy management systems on shared circuits.

Washington's primary EV-relevant utilities are Puget Sound Energy, Seattle City Light, Avista Utilities, Snohomish PUD. Always verify the applicable tariff and any utility-specific requirements (CT cabinets, metering enclosures, demand limiters) at design time.

Climate & Ampacity

Plan EV feeders against a 87°F ambient in Washington — the resulting NEC 310.15(B) correction of 0.88× is what trims a #6 THWN-2 down to its true continuous rating. Because the correction is below 0.9, conductors that "look fine" on a 30°C ampacity table will not carry their nameplate current here — always derate explicitly.

Washington takeaway

On DCFC sites with parallel feeder sets, each parallel raceway needs its own full-size EGC — a detail inspectors in Washington catch frequently on commercial submittals.