Breaker Sizing Calculator for West Virginia

NEC 2020 breaker sizing math for EV charger installers working in West Virginia.

Every EVSE branch in West Virginia is treated as a continuous load per NEC 2020 Article 625 — the OCPD must be sized at 125% of the EVSE's listed maximum draw.

Worked example for West Virginia

A 60 A continuous EV load requires a breaker rated 75 A (60 × 1.25 = 75.0 A, rounded up to the next standard size). The conductor downstream must carry that 75 A after West Virginia's 0.88× ampacity correction.

Code & Utilities

West Virginia currently enforces the NEC 2020 edition, adopted in 2022. That includes Article 625 (Electric Vehicle Power Transfer System) requirements: 125% continuous-load sizing on EVSE branch circuits, GFCI protection at outdoor receptacles, and provisions for energy management systems on shared circuits.

West Virginia's primary EV-relevant utilities are Appalachian Power, Mon Power, Potomac Edison. Each has its own service-upgrade timeline, EV rebate availability, and metering rules — confirm them before quoting commercial work.

Climate & Ampacity

Plan EV feeders against a 88°F ambient in West Virginia — the resulting NEC 310.15(B) correction of 0.88× is what trims a #6 THWN-2 down to its true continuous rating. Because the correction is below 0.9, conductors that "look fine" on a 30°C ampacity table will not carry their nameplate current here — always derate explicitly.

West Virginia takeaway

Use a 100%-rated breaker only when the panel and breaker are both listed for 100% continuous duty — otherwise the 125% rule applies. West Virginia inspectors enforce this rigorously on Article 625 work.