Box Fill Calculator for Arkansas
NEC 2020 box fill math for EV charger installers working in Arkansas.
Every EVSE installation in Arkansas eventually hits a junction or device box — disconnects, splice points, pull boxes — all of which must satisfy NEC 2020 Article 314.16 fill rules.
Worked example for Arkansas
A 4-11/16" square × 2-1/8" deep box has a 42.0 in³ volume. Each #6 Cu conductor counts as 5.0 in³. With a 2-conductor + EGC EVSE branch landing in the box plus a device, you consume roughly 15-20 in³, leaving plenty of headroom — but a 60 A multi-port pull box can fill quickly with #4 or #2 AWG conductors.
Code & Utilities
Arkansas currently enforces the NEC 2020 edition, adopted in 2022. That includes Article 625 (Electric Vehicle Power Transfer System) requirements: 125% continuous-load sizing on EVSE branch circuits, GFCI protection at outdoor receptacles, and provisions for energy management systems on shared circuits.
Major electric utilities serving Arkansas include Entergy Arkansas, Southwestern Electric Power, Arkansas Electric Cooperatives. Always verify the applicable tariff and any utility-specific requirements (CT cabinets, metering enclosures, demand limiters) at design time.
Climate & Ampacity
Plan EV feeders against a 96°F ambient in Arkansas — the resulting NEC 310.15(B) correction of 0.82× is what trims a #6 THWN-2 down to its true continuous rating. Because the correction is below 0.9, conductors that "look fine" on a 30°C ampacity table will not carry their nameplate current here — always derate explicitly.
Arkansas takeaway
Always run box-fill math when the EVSE disconnect lives more than a few inches from the unit itself — that intermediate junction is where Arkansas inspectors most often catch fill violations.