Ampacity Derating Calculator for New Hampshire

NEC 2020 ampacity derating math for EV charger installers working in New Hampshire.

New Hampshire's 87°F design ambient drives a 0.88× NEC 310.15(B)(1) correction at 75°C terminations — the single most-overlooked derate on hot-climate EV installs.

Worked example for New Hampshire

A conductor with a 30°C-rated ampacity of 95 A drops to roughly 83.6 A in New Hampshire ambient conditions. Stack a 0.8× conduit-fill adjustment (NEC 310.15(C)(1)) on top and that same conductor is only good for 66.9 A.

Code & Utilities

New Hampshire currently enforces the NEC 2020 edition, adopted in 2022. That includes Article 625 (Electric Vehicle Power Transfer System) requirements: 125% continuous-load sizing on EVSE branch circuits, GFCI protection at outdoor receptacles, and provisions for energy management systems on shared circuits.

New Hampshire's primary EV-relevant utilities are Eversource New Hampshire, Unitil, New Hampshire Electric Cooperative. Each has its own service-upgrade timeline, EV rebate availability, and metering rules — confirm them before quoting commercial work.

Climate & Ampacity

New Hampshire's representative summer design ambient is around 87°F, which yields a 0.88× ampacity correction factor at 75°C terminations per NEC 310.15(B)(1). Because the correction is below 0.9, conductors that "look fine" on a 30°C ampacity table will not carry their nameplate current here — always derate explicitly.

New Hampshire takeaway

Never size off the 30°C column in NEC Table 310.16 for New Hampshire work — always start with the temperature-corrected number, then apply any conduit-fill adjustment.