Breaker Sizing Calculator for New Hampshire

NEC 2020 breaker sizing math for EV charger installers working in New Hampshire.

Every EVSE branch in New Hampshire is treated as a continuous load per NEC 2020 Article 625 — the OCPD must be sized at 125% of the EVSE's listed maximum draw.

Worked example for New Hampshire

A 48 A continuous EV load requires a breaker rated 60 A (48 × 1.25 = 60.0 A, rounded up to the next standard size). The conductor downstream must carry that 60 A after New Hampshire's 0.88× ampacity correction.

Code & Utilities

New Hampshire currently enforces the NEC 2020 edition, adopted in 2022. That includes Article 625 (Electric Vehicle Power Transfer System) requirements: 125% continuous-load sizing on EVSE branch circuits, GFCI protection at outdoor receptacles, and provisions for energy management systems on shared circuits.

New Hampshire's primary EV-relevant utilities are Eversource New Hampshire, Unitil, New Hampshire Electric Cooperative. Each has its own service-upgrade timeline, EV rebate availability, and metering rules — confirm them before quoting commercial work.

Climate & Ampacity

New Hampshire's representative summer design ambient is around 87°F, which yields a 0.88× ampacity correction factor at 75°C terminations per NEC 310.15(B)(1). Because the correction is below 0.9, conductors that "look fine" on a 30°C ampacity table will not carry their nameplate current here — always derate explicitly.

New Hampshire takeaway

Use a 100%-rated breaker only when the panel and breaker are both listed for 100% continuous duty — otherwise the 125% rule applies. New Hampshire inspectors enforce this rigorously on Article 625 work.