Grounding Conductor Calculator for Utah

NEC 2023 grounding conductor math for EV charger installers working in Utah.

EGC sizing in Utah follows NEC 2023 Table 250.122, indexed off the upstream OCPD rating, with parallel rules for parallel sets and increased-conductor adjustments under 250.122(B).

Worked example for Utah

For a 200 A EVSE branch, Table 250.122 calls for a minimum #6 Cu equipment grounding conductor. If you upsize the phase conductors for voltage drop in Utah's long runs, NEC 250.122(B) requires the EGC to be upsized proportionally.

Code & Utilities

Utah currently enforces the NEC 2023 edition, adopted in 2024. That includes Article 625 (Electric Vehicle Power Transfer System) requirements: 125% continuous-load sizing on EVSE branch circuits, GFCI protection at outdoor receptacles, and provisions for energy management systems on shared circuits.

Utah's primary EV-relevant utilities are Rocky Mountain Power, Murray City Power, Logan Light & Power. Their make-ready, time-of-use, and demand-charge structures vary widely; pull the specific tariff before sizing service equipment.

Climate & Ampacity

Utah's representative summer design ambient is around 99°F, which yields a 0.82× ampacity correction factor at 75°C terminations per NEC 310.15(B)(1). Because the correction is below 0.9, conductors that "look fine" on a 30°C ampacity table will not carry their nameplate current here — always derate explicitly.

Utah takeaway

On DCFC sites with parallel feeder sets, each parallel raceway needs its own full-size EGC — a detail inspectors in Utah catch frequently on commercial submittals.