Breaker Sizing Calculator for Georgia

NEC 2020 breaker sizing math for EV charger installers working in Georgia.

Every EVSE branch in Georgia is treated as a continuous load per NEC 2020 Article 625 — the OCPD must be sized at 125% of the EVSE's listed maximum draw.

Worked example for Georgia

A 80 A continuous EV load requires a breaker rated 100 A (80 × 1.25 = 100.0 A, rounded up to the next standard size). The conductor downstream must carry that 100 A after Georgia's 0.88× ampacity correction.

Code & Utilities

Georgia currently enforces the NEC 2020 edition, adopted in 2021. That includes Article 625 (Electric Vehicle Power Transfer System) requirements: 125% continuous-load sizing on EVSE branch circuits, GFCI protection at outdoor receptacles, and provisions for energy management systems on shared circuits.

Georgia's primary EV-relevant utilities are Georgia Power, Oglethorpe Power, MEAG Power. Always verify the applicable tariff and any utility-specific requirements (CT cabinets, metering enclosures, demand limiters) at design time.

Climate & Ampacity

In Georgia, the 94°F summer ambient drives a 0.88× 75°C ampacity correction. Bake this into every Level 2 and DCFC conductor pick before you commit to a wire size. Because the correction is below 0.9, conductors that "look fine" on a 30°C ampacity table will not carry their nameplate current here — always derate explicitly.

Georgia takeaway

Use a 100%-rated breaker only when the panel and breaker are both listed for 100% continuous duty — otherwise the 125% rule applies. Georgia inspectors enforce this rigorously on Article 625 work.