Box Fill Calculator for Wyoming

NEC 2017 box fill math for EV charger installers working in Wyoming.

Every EVSE installation in Wyoming eventually hits a junction or device box — disconnects, splice points, pull boxes — all of which must satisfy NEC 2017 Article 314.16 fill rules.

Worked example for Wyoming

A 4-11/16" square × 2-1/8" deep box has a 42.0 in³ volume. Each #6 Cu conductor counts as 5.0 in³. With a 2-conductor + EGC EVSE branch landing in the box plus a device, you consume roughly 15-20 in³, leaving plenty of headroom — but a 60 A multi-port pull box can fill quickly with #4 or #2 AWG conductors.

Code & Utilities

The applicable code in Wyoming is the NEC 2017, which the state adopted in 2020. That includes Article 625 EVSE rules and the 125% continuous-load factor on charging branch circuits, though some 2020-cycle changes (like expanded EMS provisions) are not yet enforced statewide.

Major electric utilities serving Wyoming include Rocky Mountain Power, Black Hills Energy, Wyoming Rural Electric Cooperatives. Always verify the applicable tariff and any utility-specific requirements (CT cabinets, metering enclosures, demand limiters) at design time.

Climate & Ampacity

Wyoming's representative summer design ambient is around 90°F, which yields a 0.88× ampacity correction factor at 75°C terminations per NEC 310.15(B)(1). Because the correction is below 0.9, conductors that "look fine" on a 30°C ampacity table will not carry their nameplate current here — always derate explicitly.

Wyoming takeaway

Always run box-fill math when the EVSE disconnect lives more than a few inches from the unit itself — that intermediate junction is where Wyoming inspectors most often catch fill violations.