Wire Size Calculator for Wyoming

NEC 2017 wire size math for EV charger installers working in Wyoming.

Wire sizing in Wyoming is governed by NEC 2017 Table 310.16, with the state's 90°F summer ambient driving a 0.88× correction factor at 75°C terminations per Table 310.15(B)(1).

Worked example for Wyoming

A 100 A continuous EV branch needs a conductor whose corrected ampacity meets or exceeds 100 A. In Wyoming's 0.88× correction, that means picking a conductor whose 30°C-rated ampacity is at least 114 A. For copper THWN-2 in EMT, that typically lands at #2 AWG; aluminum requires one to two sizes larger.

Code & Utilities

The applicable code in Wyoming is the NEC 2017, which the state adopted in 2020. That includes Article 625 EVSE rules and the 125% continuous-load factor on charging branch circuits, though some 2020-cycle changes (like expanded EMS provisions) are not yet enforced statewide.

Major electric utilities serving Wyoming include Rocky Mountain Power, Black Hills Energy, Wyoming Rural Electric Cooperatives. Always verify the applicable tariff and any utility-specific requirements (CT cabinets, metering enclosures, demand limiters) at design time.

Climate & Ampacity

Wyoming's representative summer design ambient is around 90°F, which yields a 0.88× ampacity correction factor at 75°C terminations per NEC 310.15(B)(1). Because the correction is below 0.9, conductors that "look fine" on a 30°C ampacity table will not carry their nameplate current here — always derate explicitly.

Wyoming takeaway

Don't forget conduit-fill derating per NEC 310.15(C)(1) when more than three current-carrying conductors share a raceway — a common condition on multifamily and workplace EVSE home-run racks in Wyoming.