Power Calculator Calculator for New York

NEC 2017 power calculator math for EV charger installers working in New York.

Converting between kW and amps is the entry point for nearly every New York EV install spec — manufacturers publish kW, but the panel, breaker, and feeder live in amps.

Worked example for New York

A 19.2 kW EVSE draws roughly 80 A at 240 V single-phase, or 23 A at 480 V three-phase. Apply the NEC 2017 125% continuous-load multiplier before sizing the OCPD or feeder. Con Edison typically meters DCFC sites at the 480 V three-phase service in New York.

Code & Utilities

New York currently enforces the NEC 2017 edition, adopted in 2020. That includes Article 625 EVSE rules and the 125% continuous-load factor on charging branch circuits, though some 2020-cycle changes (like expanded EMS provisions) are not yet enforced statewide.

Major electric utilities serving New York include Con Edison, National Grid, PSEG Long Island, NYSEG, Central Hudson. Their make-ready, time-of-use, and demand-charge structures vary widely; pull the specific tariff before sizing service equipment.

Climate & Ampacity

New York's representative summer design ambient is around 88°F, which yields a 0.88× ampacity correction factor at 75°C terminations per NEC 310.15(B)(1). Because the correction is below 0.9, conductors that "look fine" on a 30°C ampacity table will not carry their nameplate current here — always derate explicitly.

New York takeaway

For three-phase math, always confirm the actual nameplate power factor — DCFC equipment is usually 0.95+ but older site-rated equipment can be lower, which changes the apparent power and the conductor pick.