Voltage Drop Calculator for New York

NEC 2017 voltage drop math for EV charger installers working in New York.

New York EV installs frequently push past 100 ft of conductor — detached garages, parking-lot DCFC pedestals, and multifamily carport runs all add distance. NEC 2017 recommends a 3% branch / 5% total voltage-drop ceiling.

Worked example for New York

A 48 A Level 2 charger at 240 ft on 240 V single-phase #6 Cu shows roughly 4.7% drop. That's above the 3% NEC recommendation, so you'd upsize to #4 or #2 AWG to land back under 3%. New York's 0.88× ampacity correction is independent of voltage drop but applies on the same conductor pick.

Code & Utilities

New York currently enforces the NEC 2017 edition, adopted in 2020. That includes Article 625 EVSE rules and the 125% continuous-load factor on charging branch circuits, though some 2020-cycle changes (like expanded EMS provisions) are not yet enforced statewide.

Major electric utilities serving New York include Con Edison, National Grid, PSEG Long Island, NYSEG, Central Hudson. Their make-ready, time-of-use, and demand-charge structures vary widely; pull the specific tariff before sizing service equipment.

Climate & Ampacity

New York's representative summer design ambient is around 88°F, which yields a 0.88× ampacity correction factor at 75°C terminations per NEC 310.15(B)(1). Because the correction is below 0.9, conductors that "look fine" on a 30°C ampacity table will not carry their nameplate current here — always derate explicitly.

New York takeaway

Voltage drop is a recommendation, not a hard NEC rule — but EVSEs throttle aggressively below ~228 V on a 240 V circuit, so customers in New York will notice any drop above 5%.