Grounding Conductor Calculator for Ohio

NEC 2017 grounding conductor math for EV charger installers working in Ohio.

EGC sizing in Ohio follows NEC 2017 Table 250.122, indexed off the upstream OCPD rating, with parallel rules for parallel sets and increased-conductor adjustments under 250.122(B).

Worked example for Ohio

For a 60 A EVSE branch, Table 250.122 calls for a minimum #10 Cu equipment grounding conductor. If you upsize the phase conductors for voltage drop in Ohio's long runs, NEC 250.122(B) requires the EGC to be upsized proportionally.

Code & Utilities

Ohio currently enforces the NEC 2017 edition, adopted in 2020. That includes Article 625 EVSE rules and the 125% continuous-load factor on charging branch circuits, though some 2020-cycle changes (like expanded EMS provisions) are not yet enforced statewide.

Ohio's primary EV-relevant utilities are AEP Ohio, Duke Energy Ohio, FirstEnergy, DP&L. Each has its own service-upgrade timeline, EV rebate availability, and metering rules — confirm them before quoting commercial work.

Climate & Ampacity

Ohio's representative summer design ambient is around 89°F, which yields a 0.88× ampacity correction factor at 75°C terminations per NEC 310.15(B)(1). Because the correction is below 0.9, conductors that "look fine" on a 30°C ampacity table will not carry their nameplate current here — always derate explicitly.

Ohio takeaway

On DCFC sites with parallel feeder sets, each parallel raceway needs its own full-size EGC — a detail inspectors in Ohio catch frequently on commercial submittals.