Wire Size Calculator for Ohio
NEC 2017 wire size math for EV charger installers working in Ohio.
Wire sizing in Ohio is governed by NEC 2017 Table 310.16, with the state's 89°F summer ambient driving a 0.88× correction factor at 75°C terminations per Table 310.15(B)(1).
Worked example for Ohio
A 50 A continuous EV branch needs a conductor whose corrected ampacity meets or exceeds 50 A. In Ohio's 0.88× correction, that means picking a conductor whose 30°C-rated ampacity is at least 57 A. For copper THWN-2 in EMT, that typically lands at #6 AWG; aluminum requires one to two sizes larger.
Code & Utilities
Ohio currently enforces the NEC 2017 edition, adopted in 2020. That includes Article 625 EVSE rules and the 125% continuous-load factor on charging branch circuits, though some 2020-cycle changes (like expanded EMS provisions) are not yet enforced statewide.
Ohio's primary EV-relevant utilities are AEP Ohio, Duke Energy Ohio, FirstEnergy, DP&L. Each has its own service-upgrade timeline, EV rebate availability, and metering rules — confirm them before quoting commercial work.
Climate & Ampacity
Ohio's representative summer design ambient is around 89°F, which yields a 0.88× ampacity correction factor at 75°C terminations per NEC 310.15(B)(1). Because the correction is below 0.9, conductors that "look fine" on a 30°C ampacity table will not carry their nameplate current here — always derate explicitly.
Ohio takeaway
Don't forget conduit-fill derating per NEC 310.15(C)(1) when more than three current-carrying conductors share a raceway — a common condition on multifamily and workplace EVSE home-run racks in Ohio.